Installation Manual for Snow Melting
24/7 Installation Support • Lifetime Technical Assistance • Free Design Service • www.WarmlyYours.com • (800) 875-5285
Page view 0
1 2 3 4 5 6 ... 23 24

Summary of Contents

Page 1

Installation Manual for Snow Melting24/7 Installation Support • Lifetime Technical Assistance • Free Design Service • www.WarmlyYours.com • (8

Page 2 - CONTENTS

92’ (61cm)or3’ (91cm)Length 5’ (152cm) min 50’ (1524cm) max20’ (610cm) Cold LeadOuter Sheath PVC/PololefinPolyester SheathMetal Sheath (Copper/Galvani

Page 3 - WARNING

106.0 TESTING THE MATS AND CABLE6.1 TEST ONE: INSULATION RESISTANCE (MEGOHMMETER REQUIRED)1. Connect one meter clamp to the cold lead (pigtail) inn

Page 4 - DIAGRAM A

8.0 APPENDIX A:WARMLYYOURS SNOW MELTING MATS (SUITABLE FOR ASPHALT, CEMENT AND UNDER PAVERS)Part # Size (ft/m) Voltage Area (ft2/m2) Cable Length (ft/

Page 5

APPENDIX B:WARMLYYOURS SNOW MELTING CABLES (ALL-PURPOSE FOR ASPHALT, CEMENT AND UNDER PAVERS)Part # Voltage Cable Length Total Ohms Total Watts Watts/

Page 6 - DIAGRAM B

132” to 3”(51mm to 76mm) of finished asphalt.1.5” to 2” (38mm to 51mm) of base/primer asphalt4” to 8” (102mm to 203mm) of crushed aggregateWire mesh a

Page 7

2” to 3”(51mm to 76mm) of finished asphalt.1.5” to 2” (38mm to 51mm) of base/primer asphalt4” to 8” (102mm to 203mm) of crushed aggregateWire mesh abo

Page 8

APPENDIX E:CROSS-SECTION OF SNOW MELTING CABLE IN MORTAR BED UNDER PAVERS152” to 3”(51mm to 76mm) of finished asphalt.1.5” to 2” (38mm to 51mm) of bas

Page 9

APPENDIX F:CROSS-SECTION OF INDOOR SLAB HEATING CABLE IN CONCRETE162” to 3”(51mm to 76mm) of finished asphalt.1.5” to 2” (38mm to 51mm) of base/primer

Page 10

17APPENDIX G:SNOW MELT DIAGRAM 240V - TYPICAL LINE DIAGRAM (FOR 6 CIRCUITS/CABLES) WITH PREMIUM CONTROL240V CIRCUITSAIR-SSLOW VOLTAGE (24V)LOW VOLTAGE

Page 11

APPENDIX H:SNOW MELT DIAGRAM 240V - TYPICAL LINE DIAGRAM (FOR 6 CIRCUITS/CABLES) WITH ECONOMY CONTROL240V CIRCUITSSLAB-SSLOW VOLTAGE (24V)120V CONTROL

Page 12 - 8.0 APPENDIX A:

CONTENTS1.0 Product Specications ... 12.0 Selection of the Heating Syst

Page 13 - APPENDIX B:

19APPENDIX I:SNOW MELT DIAGRAM 240V - TYPICAL LINE DIAGRAM (FOR 6 CIRCUITS/CABLES) WITH MANUAL CONTROL240V CIRCUITS120V CONTROLPOWERHeater cable pigta

Page 14 - APPENDIX C:

APPENDIX J:SNOW MELTING DIAGRAM: 240V - TYPICAL LINE DIAGRAM (FOR 6 CIRCUITS/CABLES) WITH VALUE CONTROL240V CIRCUITS120V CONTROLPOWERHeater cable pigt

Page 15 - APPENDIX D:

Installation Support • No Nonsense™ Warranty •(800) 875-5285 • www.WarmlyYours.comAPPENDIX K:SLAB HEATING DIAGRAM: 240V - TYPICAL LINE DIAGRAM (FOR

Page 16 - APPENDIX E:

Installation Support • No Nonsense™ Warranty •(800) 875-5285 • www.WarmlyYours.comWarmlyYours Snow Melting and Slab Heating WarrantyWarmlyYours, In

Page 17 - APPENDIX F:

Installation Support • No Nonsense™ Warranty •(800) 875-5285 • www.WarmlyYours.comInstall Date:Installed Under: q Concrete q Asphalt q Pavers q

Page 18 - APPENDIX G:

2.0 SELECTION OF THE HEATING SYSTEMSelection of your Heating System will depend on the application. The following can be taken as a general guide:INST

Page 19 - APPENDIX H:

4.0 INSTALLATION FOR INDOOR & OUTDOOR SLAB HEATING4.1 TEMPERATURE CONTROLLER & SENSORWe recommend a standard Programmable Thermostat with a

Page 20 - APPENDIX I:

4.3 PRE-INSTALLATION PREPARATIONS1. Review the custom installation plan for the area requiring the Heating System and verify dimensions li

Page 21 - APPENDIX J:

54.5 OPERATING TIPS1. Energy consumption will vary depending on ambient temperature and building insulation. For lower energy consumption, u

Page 22 - APPENDIX K:

65.3 INSTALLATION UNDER ASPHALT1. Ensure that paving contractor has a solid base of 4” to 8” (102 mm to 203 mm) of crushed rock aggregate tamped do

Page 23

75.4 INSTALLATION UNDER CONCRETE1. Ensure that the concrete contractor has installed a solid base of 4” to 8” (102 mm to 203mm) of crushed rock aggr

Page 24 - 10221-B 7/10

85.5 INSTALLATION UNDER PAVERS (STONE OR BRICK)1. Ensure that there is a solid base of 4” to 8” (102mm to 203mm) of crushed rock aggregate base and t